    Damage condition of the drain pan

    Picture of Drain Pan

    Picture of Furnace

    https://www.youtube.com/watch?v=LJb6oE7NH30&t=2s&ab_channel=HVACXSUPPLY

    A. How to check the drain pan conditions?
    1. Get a video camera tube sensor, insert into the furnace through Hi-
    limit sensor hole, checking above the first heat exchanger to see the
    coil drain pan’s condition.
    2. Disconnect the condensing water hose and the adapter, Open all
    screws on the coil front cover, then remove the two pieces cover
    metal away to both side, look at the bottom when you remove the two
    pieces of cover, you will see a piece of metal bar which fixed by four
    screws on side , this bar would be functioning of support the front of
    coil. After you remove this bar, then you have enough gap to check
    the bottom of inside of coil with that camera.

    B. How to replace the coil drain pan?

    1. Pumpdown refrigerant of the system first, open outdoor unit cover, hook
    up pressure gauge to suction port, fully turn off the liquid port shut off valve
    , and turn off suction port valve in half or more, press SW1 for 5”, untill
    LED blinking, then press SWI until 08, then press SW2 for starting pumping
    down. When it is processing, monitoring the suction port pressure, fully turn
    off the suction line valve when the pressure is going to 0, and also you
    would get a error code of E3 . You have completed the pumpdown
    procedures. Then disconnect power of 240v from service box.
    2. Disconnect two flaring connections from indoor cased coil, try remove
    bit for enough space to pull out the coil from the case. unscrews all on the
    case cover, also you need to remove the support metal strip on right, and
    two screws which are fixed the side drain pan on left top outside, remove
    the support L-shaped sheet, then you can try to move the coil out of the
    case.
    3. Remove two screws on the pan which fixed with coil on both side, then
    you will get a naked copper coil .

    4. Replace with the new black plastic drain pan, get rid of the spare side
    drain pan and L-shaped support, if you are installing in vertical. Next you
    need slide the coil with new drain pan into the case, remember that metal
    pan at the bottom of coil still attached. getting all cover screws back on,
    and reconnecting the flaring with two copper line set. Please note, when
    you reconnecting the flaring, apply some Nylog for good sealing would be
    very necessary.
    5. Repeat as a new installation to pressure test and vaccum system as
    required, then release refrigerant from compressor. Done